How many BTU do I need for a 12×12 room?

September 2022 · 6 minute read

Calculated BTU:

If you want to properly cool down a 300 square foot area (or room), you need a 6,000 BTU air conditioner. Obviously, the problem arises when you have a tiny 12×12 room, for example. According to the US Department of Energy directive, an air conditioner’s most appropriate size would be 2,880 BTU unit.

Moreover, How many BTU is 2400 square feet?

For example, if the bedroom and office area zone is 1,800 square feet and the living areas and kitchen are 2,400 square feet, add together the recommended BTUs for each. You’ll need between about 180,000 and 280,000 total BTUs for your home based on the climate and house factors considered in the calculator.

What size room will 5000 BTU?

The size of your space determines how much cooling capacity you need. Budget air conditioners range from 5,000 BTU, which can handle about 150 square feet, to 12,000 BTU, enough to cover about 550 square feet.

Also Is a higher Btu better? BTU – British Thermal Unit – BTU is a very common term when it comes to HVAC equipment. One BTU is the amount of energy it takes to raise one pound of water one degree Fahrenheit. The higher the BTUs, the more power the system has.

How do I calculate BTU for my house?

The rule of thumb for calculating the right BTUs for your home is to take the overall square footage of your living space and multiply it by a factor of BTUs/square foot (don’t worry, there’s an example of how to do this further down this article).

24 Related Questions Answers Found

How do I calculate BTU needed?

For example, a 300 square foot room typically requires 7,000 BTUs to maintain a comfortable temperature, while a 1,000 square foot room requires 18,000 BTUs. A simple formula to determine your heating needs is: (desired temperature change) x (cubic feet of space) x . 133 = BTUs needed per hour.

Is 8000 BTU enough for a bedroom?

Recommended BTU By Room Size

If you are looking for an air conditioner for a room measuring say 10′ x 15′ (150 square feet), the recommended BTU range is up to 5400. … Once you get into 340 and 400 square feet per room, you’d need an 8,000 or 9,000 BTU air conditioner, respectively.

How do I calculate BTU for air conditioner?

To calculate the size, simply multiply the length times the width of the room or area to be cooled. Then, as a practical number, multiply that total times 25 BTU. This allows ample cooling, whether it is a rainy, moist day or a hot, sunny, humid day.

Is 5000 BTU enough for a bedroom?

A 5000 BTU air conditioner is suitable for cooling a room that’s 100-150 sq. … If placed in a bigger room, it will result in energy inefficiency because the AC will run for longer to cool the room. On the upper scale, a 12,000 BTU AC is good for a 450-550 sq. ft room.

Is 5000 BTU enough for a living room?

A 5,000 Btu air conditioner can effectively cool a room that measures 100 to 150 square feet, according to a basic industry standard.

How many BTU do I need for a 20×20 room?

BTU Chart for Sizing an Air Conditioner

Room/Area Size:Examples:Recommended BTU:
100-200 sq ft10×12-10×20, 12×15, 14×14 rooms6,000 BTU
200-300 sq ft10×20-15×20 rooms, efficiency apartment8,000 BTU
300-400 sq ft15×20-20×20 rooms, studio apartment
10,000 BTU
400-500 sq ft20×20-20×25 rooms, 1-bedroom apartment12,000 BTU

How many square feet will 40000 BTU heat?

To heat a 2,000 square foot home, you will need approximately 40,000 BTU’s of heating power.

What size BTU do I need?

As a rule of thumb, an air conditioner needs 20 Btu for each square foot of living space. But other considerations, such as the ceiling height and the size of your windows and doorways, might call for more cooling power. To measure your room, multiply the length by the width.

How many square feet will 40000 Btu heat?

To heat a 2,000 square foot home, you will need approximately 40,000 BTU’s of heating power.

How many BTU do I need for 700 square feet?

2. Find the correct cooling capacity for your room size

Area To Be Cooled (square feet)Capacity Needed (BTUs per hour)
400 up to 45010,000
450 up to 55012,000
550 up to 700
14,000
700 up to 1,00018,000

Are higher BTUs better?

A heater with a higher BTU rating is more powerful — that is, it has a higher heat output — than one with a low BTU rating. It can do more to raise the temperature in your room each hour, so you can either heat a room more quickly or heat a larger space.

Is 12000 Btu too much?

The most common window air conditioning units come in cooling capacities ranging from 5,000 to 12,000 Btu. A 12,000 Btu air conditioner can cool between 450 and 550 square feet of floor space. A 12,000 Btu unit could cool a room 25 feet long by 20 feet wide that has 500 square feet of floor area.

How many square feet will 12000 Btu cool?

12,000 BTUs will cover 400 sq. ft. (3,200 cubic feet)

Is there a big difference between 5000 BTU and 6000 BTU?

Keep in mind that a 5000 BTU AC is rated for “up to” 150 square feet and a 6000 BTU unit is rated for “up to” 250 square feet. In simple terms, that a room 10×15 (150 square feet) or about 15×17 (about 250 square feet). Those are the biggest areas these units can effectively cool and dehumidify.

How big of a room will a 6000 BTU cool?

You’ll need to know your room size too. In general, a 5,000 to 6,000 BTU air conditioner can cool between 100 and 300 square feet. Seven thousand to 8,200 BTU units are adequate for cooling 250 to 550 square feet, while 9,800 to 12,500 BTU models cool up to 950 square feet.

What size room will 12000 Btu cool?

12,000 BTUs will cover 400 sq. ft. (3,200 cubic feet) 13,000 BTUs will cover 450 sq.

Is 6000 BTU enough for a living room?

Consumer Reports recommends 20 BTUs per square foot of the living space (or spaces) you want to cool down. … 150 – 250 sq. feet: 6,000 BTUs.

Is 400 sq ft small?

How big is a 400-square-foot apartment? Four-hundred square feet is about the size of a two-car garage. It’s not a huge apartment, but it’ll get the job done. After all, two cars take up a lot of space and you won’t actually have two cars parked in your house — the furniture you have will be much smaller!

Does higher Btu use more gas?

The higher the BTU capacity of a gas burner, the hotter the burner can get; the hotter the burner, typically the faster the cooking times. But while BTU measures heat production, it doesn’t necessarily translate into better cooking performance. … Some ranges “cycle” heat for low-temperature cooking.

ncG1vNJzZmiZlKG6orONp5ytZ5ikxG65wKewZpqkqnqlu4yiZKedlZl6p7vRZphmaWKtfnN50aimpmVmZA%3D%3D